Concrete Spalling: Causes, Rebar Corrosion and Repair

Concrete spalling is the breaking away of concrete cover, and in reinforced concrete it starts where steel corrodes and its rust takes up more space than the steel it replaces. A spall that shows rusted bar and a flaking driveway surface look alike from a distance, so which repair does each one need? Spalled concrete over corroding steel, also called concrete cancer, is a corrosion problem first and a surface problem second.

Steel in sound concrete sits in pore water at pH 13 to 13.8 and stays passive until chlorides reach about 0.05 to 0.1 % by mass of concrete at the bar or carbonation lowers the pH around it. Every durable spall repair removes that cause, rebuilds the cover with a classed repair mortar and protects the patch edge, and spalling is one of the problem areas covered across construction chemicals.

This page covers spalling versus scaling and honeycombing, the thresholds, the repair geometry of about 19 mm (3/4 in) behind every corroded bar, the survey, 14 product classes in job order, safety and VOC rules, and dated costs such as USD 538 to 1,615 per m² (USD 50 to 150 per ft²) for installed spall repair with rebar treatment in the US (blog cost guide, 2026-03).

Standards, codes and regulations are checked against their issuing bodies, product values against the named data sheet and prices against the dated source named in the sentence; see our methodology and fact-checking.

What Is Concrete Spalling?#

Spalling is the loss of pieces of concrete from the surface or edge of a member, and in reinforced concrete it starts at the steel, where corrosion products build pressure under the cover until it breaks off. Corrosion of the bar needs both water and oxygen, so a spall forms where both reach the steel through the cover. The expansion cracks the concrete along the bar before a piece separates, so a patch over the surface alone leaves the corroding steel behind.

Spalled, Scaled or Honeycombed: Telling Surface Defects Apart#

Spalling, scaling and honeycombing are three different defects, and the repair route follows the cause, not the look of the surface. Scaling, per the ACI definition, is local flaking or peeling of the near-surface portion of hardened concrete or mortar; on parking decks the surface loss can exceed 25 mm (1 in), yet no steel is exposed. Honeycombing is a placing defect: voids left by incomplete filling of the formwork or poor compaction, sorted into small voids under 10 mm (0.4 in), medium voids of 10 to 50 mm (0.4 to 2 in) and large voids over 50 mm (2 in).

Why is my concrete flaking? Flaking without steel is scaling, the surface defect, while a crack that runs along a bar is the first stage of a corrosion spall and belongs to the corrosion route. Cracks caused by corroding reinforcement are not repaired by epoxy injection, because the resin seals the rust in without stopping it.

Table D1 compares what each defect removes, whether steel shows and the first repair route.

Defect What is lost Steel exposed? First route
Spalling pieces of cover over corroding bar yes, in a corrosion spall survey, break out, treat steel
Scaling local flaking or peeling of the near-surface layer; can exceed 25 mm (1 in) on decks no surface repair
Honeycombing voids from incomplete filling or compaction; small under 10 mm (0.4 in), medium 10 to 50 mm (0.4 to 2 in), large over 50 mm (2 in) sometimes size class decides
Crack along a bar crack following corroding reinforcement not yet corrosion route, never epoxy injection

What Causes Concrete to Spall?#

Concrete spalls when its reinforcement corrodes, started either by chlorides from de-icing salts or seawater reaching the steel or by carbonation lowering the alkalinity of the concrete around it. Both routes end the same way: the steel loses its passive film, rust forms, and the expansion breaks the cover. Alkali-silica reaction and mix-design durability are covered on concreteadditives.net.

Corroding Reinforcement: How Chlorides and Carbonation Break the Cover#

Steel in sound concrete is protected by pore water at pH 13 to 13.8, and it starts to corrode when chlorides reach a threshold at the bar or carbonation drops the pH around it. The alkalinity keeps a passive film on the steel.

Chlorides break that film locally. NRMCA puts the chloride needed to initiate corrosion at 0.05 to 0.1 % by mass of concrete, about 1.2 to 2.4 kg/m³ (2 to 4 lb/yd³), or about 0.4 to 0.8 % by mass of cement for a mix with about 297 kg/m³ (500 lb/yd³) of cement. NRMCA also notes that 50 to 75 % of the total chloride is water-soluble, so the test method matters when a result is compared with a limit.

Carbonation works more slowly and over the whole surface. Carbon dioxide reacts with calcium hydroxide in the paste (Ca(OH)2 + CO2 → CaCO3 + H2O), the carbonation depth grows roughly with the square root of age, and WJE places the fastest carbonation at 50 to 70 % internal relative humidity. NPCA gives about 1 mm (0.039 in) per year in high-quality, low w/cm concrete. How low must the pH fall? Sources differ: NRMCA gives below 9, WJE about 9.5, and the Concrete Society puts the loss of passivity at about 11.

De-Icing Chlorides: Surface Damage and Corrosion Together#

De-icing salts attack concrete twice: at the surface, where they drive scaling, and at depth, where their chlorides reach the reinforcement. On parking structures, ACI 362.2R-00 names water and de-icing chlorides carried through the slab as the deterioration driver, and the current maintenance guide is ACI PRC-362.2-21. The laboratory test for deicer scaling, ASTM C672/C672M-12, was withdrawn in 2021 without a replacement, so scaling resistance is no longer specified by an active ASTM method.

Spalling on Driveways, Garage Floors and Foundation Walls#

On driveways, garage floors and foundation walls, one test decides the route: damage that exposes rusted steel is a corrosion spall, and damage in the top layer without steel is surface scaling. Concrete driveway spalling and concrete floor spalling without visible steel therefore follow the scaling route, not the corrosion route.

Flatwork without exposed steel goes to a surface repair class: a cosmetic patch, a rapid-hardening mortar where the slab must reopen fast, or a resurfacer over worn but sound concrete. A foundation wall that spalls while water comes through it needs the water stopped first, under basement waterproofing, and the concrete repair second.

Spalling Thresholds: Chloride, pH, Cover and Repair Geometry#

Spall repair runs on a short list of numbers: steel stays passive at pH 13 to 13.8, corrosion can start at about 0.05 to 0.1 % chloride by mass of concrete, and a repair clears about 19 mm (3/4 in) behind every corroded bar. The ACI 318-19 chloride limits in Table N1 are design limits for new concrete, not repair triggers. Table N1 lists each threshold, what it governs and the document it comes from.

Value Governs Basis
pH 13 to 13.8 pore solution of sound concrete; steel passive NRMCA
pH below about 9 carbonated concrete can initiate corrosion NRMCA (WJE about 9.5; Concrete Society about 11)
0.05 to 0.1 % by mass of concrete, about 1.2 to 2.4 kg/m³ (2 to 4 lb/yd³); about 0.4 to 0.8 % by mass of cement chloride to initiate corrosion NRMCA, assumes about 297 kg/m³ (500 lb/yd³) cement
50 to 75 % water-soluble share of total chloride NRMCA
1.00 / 0.30 / 0.15 % (C0 / C1 / C2); 0.06 % prestressed maximum water-soluble chloride by mass of cementitious materials, new concrete ACI 318-19 Table 19.3.2.1
about 1 mm (0.039 in) per year carbonation in high-quality, low w/cm concrete NPCA
50 to 70 % internal RH fastest carbonation WJE
about 19 mm (3/4 in) clearance behind corroded bar, full circumference ICRI 310.1R-2008 practice
about 19 mm (3/4 in) deep rectangular edge saw cut, no re-entrant corners ICRI 310.1R-2008 practice
6 mm (1/4 in) or more substrate roughness amplitude ICRI 310.1R-2008 practice
R4 ≥ 45 MPa (6,527 psi), bond ≥ 2.0 MPa (290 psi); R3 ≥ 25 MPa (3,626 psi), bond ≥ 1.5 MPa (218 psi) structural repair mortar classes EN 1504-3:2005
≤ 0.05 % chloride ion content of repair mortar, all classes EN 1504-3:2005
≤ 110 mA/m² (10.2 mA/ft²) long-term; ≤ 220 mA/m² (20.4 mA/ft²) short-term current density at the anode surface ISO 12696:2022 clause 6.2.1
sD,CO2 > 50 m (164 ft) anti-carbonation coating, principle 1 EN 1504-2:2004 (EN 1062-6)

EN 1504, ACI and ICRI: The Documents Behind a Spall Repair#

European spall repair follows the principles of EN 1504-9:2008 and the product classes of EN 1504-3:2005, while US practice follows ACI and ICRI guides. EN 1504-9:2008 groups reinforcement corrosion under principles 7 to 11: preserving or restoring passivity, increasing resistivity, cathodic control, cathodic protection and control of anodic areas. Methods 7.1 (increasing cover) and 7.2 (replacing contaminated or carbonated concrete) use EN 1504-3:2005 mortars. Only classes R3 and R4 are structural; R1 and R2 are not, and the carbonation resistance test applies to R3 and R4 alone. EN 1504-3:2005 covers cementitious, polymer-modified and resin-bound (PC) mortars, and it is still the cited edition under the Construction Products Regulation (EU) 2024/3110, in force since 2025-01-07 and applicable since 2026-01-08.

US repair work draws on ACI PRC-546-23, the Concrete Repair Guide, ACI PRC-546.3-23 for materials selection and ACI SPEC-563-25 for repair of concrete in buildings. ICRI 310.1R-2008 covers surface preparation of concrete damaged by reinforcing steel corrosion, ICRI 210.5R-2026 sets reinforcing bar cleaning levels and ICRI 110.1R-2026 is the guide specification for structural concrete repair, Section 03 01 30. EN 1504-9 is not a product standard, and every part and its status are listed under EN 1504.

How Is Spalled Concrete Assessed Before Repair?#

A spall survey maps three things before any repair is priced: where the concrete is delaminated, how far chlorides or carbonation have reached, and where the steel is still corroding. The five tests below answer those questions and, after the repair, prove the bond.

  1. Delamination: hammer sounding or chain drag marks the hollow areas around visible spalls, where the cover has already separated.
  2. Corrosion potential: half-cell potential testing to ASTM C876-22b maps potentials on a grid; the current edition sets no pass/fail, does not apply with epoxy-coated reinforcement or membranes between steel and surface, and is read by specialists with other data (ICRI 510.3-2025 is the ICRI guide).
  3. Chloride profile: chloride testing of concrete uses ASTM C1152/C1152M-20 (acid-soluble), ASTM C1218/C1218M-20 (water-soluble), EN 14629:2007 or AASHTO T 260-21, on powder drilled at 5 to 25, 25 to 50 and 50 to 75 mm (0.2 to 1, 1 to 2 and 2 to 3 in), with the first 5 mm discarded and at least 25 g per depth.
  4. Carbonation depth: phenolphthalein sprayed on a fresh break or core turns pink above about pH 8 to 9.5 and stays colorless below (EN 14630:2006), tested within 15 minutes of cutting; the Concrete Society notes that the pH change runs a few millimeters ahead of the color boundary.
  5. Repair bond: pull-off adhesion testing to ASTM C1583/C1583M-25 or EN 1542, with ICRI 210.3R-2022 as the guide, checks the substrate before and the patch after repair.

Survey results set the break-out limits and the protection strategy. A chloride profile above the initiation range at bar depth beyond the visible spall tells the engineer that new corrosion will start next to a plain patch, which is the case for galvanic anodes or wider removal.

Which Repair Systems Fit Which Spall?#

A spall repair is a sequence, not a single product: the steel is exposed and cleaned, coated or fitted with anodes, the section is rebuilt with a repair mortar of the right class, and the surface is protected so the next spall does not start beside the patch. A specification should name the spall condition first and the product class second. Table S1 lists 14 rows in job sequence, from coating the steel to sealing the surface, and ends with the products that are not the answer.

# Product class Spall condition Job Governing document (edition) Structural?
1 rebar corrosion protection coatings cleaned bar in the patch coat the steel EN 1504-7:2006 (EN 15183; EN 15184 ≥ 80 % of reference bond) n/a
2 galvanic anodes chloride-contaminated concrete around the patch anode tied to the bar before patching; halo control ISO 12696:2022; EN 1504-9:2008 principle 10 n/a
3 concrete bonding agents prepared substrate bond or scrub coat where the mortar system calls for one per mortar system n/a
4 concrete repair mortars corrosion spall in a structural member reprofile, restore cover EN 1504-3:2005 R3 / R4 yes (R3, R4)
5 epoxy mortars thin, chemical-resistant or very high-strength patches resin-bound reprofiling EN 1504-3:2005 R4 (PC mortar); ASTM C579-23 test yes
6 rapid-hardening repair mortars pavements, decks, ramps reopened in 1 to 3 h fast reprofiling ASTM C928/C928M-25 R1 to R3 depends
7 shotcrete large areas, overhead, section enlargement sprayed reprofiling ACI SPEC-506.2-13 (reapproved 2018); EN 14487-1:2022 yes (f'c ≥ 28 MPa (4,000 psi), ACI 506R-16)
8 FRP strengthening systems capacity lost to section loss add capacity ACI PRC-440.2-23, ACI CODE-440.13-24, ICC-ES AC125 (April 2025) yes
9 concrete resurfacers worn but sound flatwork, no steel thin topping none specific no
10 concrete patching compounds cosmetic shallow patch up to 6 mm (1/4 in), no steel non-structural patch EN 1504-3:2005 R1 at most no
11 surface-applied and migrating corrosion inhibitors sound but contaminated concrete slow corrosion without removal EN 1504-9:2008 method 11.3 (no product part) no
12 anti-carbonation coatings carbonating facades, bridges, car parks slow CO2 ingress EN 1504-2:2004 (sD,CO2 > 50 m (164 ft)) no
13 penetrating sealers and water repellents decks and walls taking water and chlorides hydrophobic impregnation EN 1504-2:2004; SCAQMD Rule 1113 sealers 100 g/L (0.83 lb/gal) no
14 not the answer: tar or asphalt patches; epoxy injection of cracks caused by corroding steel any corrosion spall none none no

Break Out, Clean the Steel and Reprofile: The Standard Spall Repair#

The standard repair removes all delaminated and contaminated concrete, clears about 19 mm (3/4 in) around the full circumference of every corroded bar, and saw-cuts a rectangular edge about 19 mm deep with no re-entrant corners. The dimensions follow ICRI 310.1R-2008 practice. Chipping hammers of 6.8 kg (15 lb) are the preferred size for break-out, and the prepared substrate needs a roughness amplitude of 6 mm (1/4 in) or more. Roughness and cleanliness are specified as a concrete surface profile, and profiles and preparation methods are graded under concrete surface profile.

Once exposed, the steel is cleaned to a stated level: ICRI 210.5R-2026 is the guide for selecting and specifying reinforcing bar cleaning levels. A cleaned bar can then take a protective coating to EN 1504-7:2006, either an active coating (method 11.1) or a barrier coating (method 11.2), proved by the EN 15183 corrosion test and an EN 15184 bond of at least 80 % of the uncoated reference. Bruising, the microcracked layer left by aggressive removal, is the subject of ACI PRC-364.7-21, and a bruised layer is removed before the mortar goes in.

The section is rebuilt with a repair mortar whose class matches the member: EN 1504-3:2005 R3 or R4 for anything structural, R4 needing at least 45 MPa (6,527 psi) and 2.0 MPa (290 psi) bond, R3 at least 25 MPa (3,626 psi) and 1.5 MPa (218 psi). The substrate is brought to saturated surface dry and receives a scrub coat of neat mortar or a primer where the mortar system calls for one. Three failure modes recur: debonding from a dusty, dry or bruised substrate, R1 or R2 mortar used structurally and later re-attacked by carbonation or chlorides, and corrosion at the patch perimeter. A pull-off test to ASTM C1583/C1583M-25 checks the bond once the mortar has cured.

Stopping the Next Spall: Anodes, Inhibitors and Protective Coatings#

A patch in chloride-contaminated concrete can trigger new corrosion around its edge, the halo or ring-anode effect, and galvanic anodes, inhibitors and coatings are the three ways to slow it. A zinc anode tied to the bar corrodes preferentially and supplies protective current, preventing new anodes from forming next to the repair. ISO 12696:2022 limits the current density at the anode surface to 220 mA/m² (20.4 mA/ft²) short-term and 110 mA/m² (10.2 mA/ft²) long-term (clause 6.2.1), and its clause 6.1 note states that galvanic anode systems used without monitoring do not comply with the standard. Anode layout and zinc mass are designed by a corrosion engineer.

Inhibitors are the weaker evidence base. EN 1504-9:2008 lists them as method 11.3, without an EN 1504 product part. Sprinkel (Virginia Transportation Research Council, 2003, VTRC 03-R14) found no measurable corrosion reduction from inhibitors in slabs at 1.8 to 5.9 kg/m³ (3 to 10 lb/yd³) chloride, and FHWA-HRT-22-087 (2022) found overlay bond reduced by as much as 80 % after 2 years of chloride ponding where an inhibitor was applied to the substrate. Anti-carbonation coatings to EN 1504-2:2004 need a CO2 diffusion resistance sD,CO2 above 50 m (164 ft), and mortars, anodes and inhibitors are compared under concrete repair products.

Large, Overhead and Structural Spalls: Shotcrete and FRP#

Where spalls are large, overhead or have cost the member capacity, sprayed mortar rebuilds the section and FRP adds strength, both after an engineer has assessed the member. Shotcrete follows ACI PRC-506-22, the shotcrete guide, and ACI SPEC-506.2-13 (reapproved 2018) in the US, and EN 14487-1:2022 in Europe; ACI 506R-16 defines structural shotcrete as a specified f'c of at least 28 MPa (4,000 psi). Externally bonded fiber-reinforced polymer restores flexural, shear or confinement capacity lost to section loss, designed to ACI PRC-440.2-23 and ACI CODE-440.13-24 and evaluated in the US under ICC-ES AC125 (April 2025 edition).

Shallow Spalls on Flatwork: Patching, Rapid-Hardening Mortars and Resurfacers#

A shallow spall in a slab without exposed steel needs a surface repair, and the choice between a patch, a rapid-hardening mortar and a resurfacer depends on depth, traffic and how fast the slab must reopen. Cosmetic patching compounds fill shallow damage up to about 6 mm (1/4 in) and rate no higher than EN 1504-3 R1. Rapid-hardening repair materials fall under ASTM C928/C928M-25, which covers packaged dry cementitious materials for rapid repairs in classes R1 to R3 and lets pavements, decks and ramps return to traffic in 1 to 3 h. ASTM C928 class R3 is unrelated to EN 1504-3 class R3, so a data sheet stating "R3" names its standard.

Resurfacers cover worn but sound flatwork with a thin topping and have no specific product standard. A tar or asphalt patch is not a spall repair, and spalls are never patched with tar or asphalt.

The repair route for a spall changes with the structure: parking decks and bridges carry de-icing chlorides, marine structures sit in the splash zone, and facades and balconies lose cover to carbonation. Table A1 matches 9 topics and structures with their spall driver, the first repair route and the key document.

Topic or structure Spall driver First route Key document
rebar corrosion in concrete chlorides or carbonation at the bar survey, break out, anodes NRMCA; ISO 12696:2022
concrete carbonation low cover, carbonated zone depth test, anti-carbonation coating EN 14630:2006
concrete scaling de-icers and freeze-thaw at the surface surface repair ASTM C672/C672M-12 (withdrawn 2021)
honeycombing in concrete placing defect repair by size class size classes under 10 mm, 10 to 50 mm, over 50 mm
concrete crack repair cracks along bars corrosion route, not injection ACI PRC-546-23
parking structure repair de-icing chlorides through the deck repair plus traffic coating ACI 362.2R-00; ACI PRC-362.2-21
bridges, tunnels and marine structures chlorides, traffic EN 1504-9 principles EN 1504-9:2008
marine concrete repair splash zone chlorides anodes, sprayed mortar ISO 12696:2022
basement waterproofing water through foundation walls stop water, then repair ACI PRC-546-23

Safety and VOC Rules for Spall Repair Materials#

Spall repair exposes crews to cement, crystalline silica and, with epoxy mortars, epoxy resins, and each has its own rule. Portland cement in repair mortars carries the line "No Annex VI entry; ECHA C&L notified classification: H315, H317, H318, H335"; see the product SDS. REACH Annex XVII entry 47 limits soluble Cr(VI) to 2 mg/kg (0.0002 %) of the total dry weight of the cement when hydrated.

Break-out, saw-cutting and abrasive blasting release respirable dust from quartz (crystalline silica) in the concrete and sand. OSHA 29 CFR 1926.1153 limits respirable crystalline silica in construction to a PEL of 50 µg/m³ as an 8-hour TWA, with an action level of 25 µg/m³, effective 2016-06-23; for the classification of a silica-bearing product, see the product SDS. Epoxy mortars bring the resin hazard: liquid epoxy resin (CAS 25068-38-6) is harmonized under CLP Annex VI index 603-074-00-8 with H315, H317, H319 and H411, and for the amine hardeners, see the product SDS.

VOC rules apply to the coatings and sealers that protect a repair, not to the mortar. South Coast AQMD Rule 1113 (amended 2016-02-05) has no repair-mortar or patching category, so a coating over a repair falls under its own coating category; Waterproofing Concrete/Masonry Sealers are limited to 100 g/L (0.83 lb/gal), and a Proposed Amended Rule 1113 is at working-group stage. Outside the South Coast, EPA AIM (40 CFR 59 subpart D, products made on or after 1999-09-13) allows 600 g/L (5.01 lb/gal) for waterproofing sealers and 400 g/L (3.34 lb/gal) for concrete protective coatings, and every category is listed under VOC limits for construction chemicals.

How Is Spall Repair Bought? Scope, Specification and Cost#

Spall repair is bought by measured area or volume of removal and repair, and a usable quote states the survey, the removal limits, the mortar class, the steel treatment, any anodes and the acceptance test. ICRI 130.1R-2009, the Guide for Methods of Measurement and Contract Types for Concrete Repair Work, sets out how quantities are measured and paid, and ICRI 110.1R-2026 gives the guide specification, Section 03 01 30, that ties the scope to the drawings.

Four dated public ranges exist, and all come from cost guides rather than bid records. General installed concrete repair costs USD 149 to 177 per m² (USD 13.82 to 16.43 per ft²) in the US (Homewyse cost guide, 2026-01). A blog cost guide (aerially.ai, 2026-03) gives installed minor spall patches at USD 215 to 538 per m² (USD 20 to 50 per ft²) and installed spall repair with rebar treatment at USD 538 to 1,615 per m² (USD 50 to 150 per ft²) in the US. Table C1 lists the four ranges with their scope, date and source.

Scope (as published) Basis USD per m² (USD per ft²) Region Date Source
concrete repair, general installed 149 to 177 (13.82 to 16.43) US 2026-01 Homewyse, cost guide
minor spall patch installed 215 to 538 (20 to 50) US 2026-03 aerially.ai, blog cost guide
spall repair with rebar treatment installed 538 to 1,615 (50 to 150) US 2026-03 aerially.ai, blog cost guide
spalling or scaling repair, residential flatwork installed 32 to 54 (3 to 5); USD 1,800 to 4,200 for a 56 m² (600 ft²) driveway US 2025-12 HomeGuide
surface vs full-depth structural repair basis not stated 54 to 108 vs 323 to 538 (5 to 10 vs 30 to 50) US 2025-05 zavzaseal.com, contractor blog

Three factors drive the price: depth, steel treatment and access. A surface repair on flatwork without steel stays at the low end, while a structural repair adds break-out behind the bar, steel cleaning, coating or anodes, formwork or spraying, and the pull-off tests. Access adds scaffold, lifts or traffic control, and no dated public range covers galvanic anodes, so their cost is priced from the survey and the anode layout.

Who Repairs Spalled Concrete?#

Structural spall repair is specialist work, carried out by a repair contractor to an engineer's survey, while a cosmetic patch on flatwork without exposed steel is a surface repair outside the structural scope. The engineer sets the removal limits and the mortar class from the survey; the contractor breaks out, treats the steel, reprofiles and tests.

Two roles sit beside the crew. The ICRI Concrete Surface Repair Technician (CSRT) education and certification course is a QC/QA and inspector credential for people checking repair work, not an applicator requirement. Galvanic anode systems are designed by a corrosion engineer.

Will Spalling Concrete Get Worse?#

Yes, a corrosion spall keeps growing while water, oxygen and chlorides still reach the steel, so repair stops the spread only when it removes the cause.

A spall left in place widens as rust forms under the next stretch of cover. Basements, parking decks, bridges and the other structures and problems are listed under construction chemicals by application.

How serious is concrete spalling?#

Spalling is serious when it exposes reinforcement in a load-bearing member, and cosmetic when it stays in the top layer of a slab without steel. A member that has lost bar section goes to an engineer for assessment before any repair.

What is the best product to repair spalling concrete?#

No single product is best: a structural spall takes a repair mortar declared to EN 1504-3:2005 class R3 or R4, and a declaration of performance or data sheet shows the class. A shallow flatwork spall without steel takes a patching compound, a rapid-hardening mortar to ASTM C928/C928M-25 or a resurfacer, chosen by depth and reopening time.

Can spalled concrete be resurfaced instead of repaired?#

Only when no steel is exposed: a resurfacer covers worn but sound concrete, while a corrosion spall under it keeps spreading. Concrete resurfacers bond as a thin topping to sound flatwork, so the spall is first broken out and repaired, and the resurfacer then evens the surface.